ThermoDyne

Indirect Fired Water Heater

Thermodyne Storage Type/ Semi-Instantaneous Water Heaters


Space saving, factory packaged, quick recovery water heaters.

Tank Specifications:

  • Copper Alloy construction throughout
  • Size from 16” dia. x 33” high to 30” dia. x 40” high
  • Forced internal circulation
  • Ready for service connections.
  • Built to code requirements

Typical Applications

Hospitals, industrial plants, prisons, universities and all facilities requiring high hot water demands with limited space.
     TDyne.gif
    Tdyne.jpg


     Technical Data
    TDyne.gif

    TDyneArt.gif

      Selection Tables

    Coil Selection shown in Gallons per Minute
    Steam Line Pressure
    2
    5
    10
    15
    25
    40
    50
    75
    100
    Steam Pressure in Element
    0
    2
    5
    10
    15
    25
    30
    50
    65
    Temp. Range: 40 degrees
    to
    120
    degrees
    16-051
    12
    13
    14
    15
    16
    17
    18
    21
    22
    16-061
    19
    21
    23
    24
    26
    27
    28
    31
    33
    16-081
    36
    38
    40
    42
    44
    48
    53
    55
    58
    16-082
    40
    44
    48
    53
    57
    60
    64
    69
    72
    18-101
    51
    60
    66
    71
    75
    79
    85
    89
    94
    20-102
    64
    81
    89
    96
    100
    120
    128
    151
    157
    20-121
    89
    98
    112
    129
    145
    158
    162
    171
    177
    24-122
    104
    106
    118
    132
    148
    163
    168
    178
    184
    30-141
    124
    136
    152
    164
    180
    186
    201
    217
    250
    30-142
    144
    155
    179
    189
    201
    241
    265
    273
    287
    Temp. Range: 40 degrees
    to
    140
    degrees
    16-061
    14
    15
    17
    19
    21
    24
    26
    27
    30
    16-082
    27
    30
    34
    39
    43
    51
    56
    56
    60
    18-101
    36
    36
    42
    46
    54
    57
    60
    63
    72
    20-102
    51
    56
    59
    66
    69
    83
    89
    106
    109
    24-122
    87
    88
    99
    113
    124
    132
    134
    136
    138
    30-142
    102
    113
    127
    153
    180
    223
    238
    245
    275


     Heater Dimensions in Inches

    Model
    Dimensional Guide Letters

    A
    B
    C
    D&E
    F (OAH)
    G (Drain)
    H
    16-051
    16
    33
    57
    2
    33.25
    .75
    16.5
    16-061
    16
    33
    57
    2.5
    32.5
    .75
    16.5
    16-081
    16
    33
    50
    3
    32.5
    .75
    16.5
    16-082
    16
    33
    57
    3
    32.5
    .75
    16.5
    18-101
    18
    34
    49
    4
    33
    .75
    18.5
    20-102
    20
    35
    56
    4
    33.5
    .75
    20.5
    20-121
    20
    35
    56
    4
    33.5
    .75
    20.5
    24-122
    24
    39
    64
    5
    33.5
    .75
    24.5
    30-141
    30
    40
    61
    6
    36
    .75
    30.5
    30-142
    30
    40
    67
    6
    36
    .75
    30.5